Aquastrong CDS036 Mini Split Condensate Pump

Aquastrong's CDS036 is a two-piece mini pump for ductless heads and cassettes, listed for 9.6 GPH and a 33 ft lift, with a small sensor tank and both normally closed and normally open safety contacts.

Model CDS036 · part number CDS036-1 · Updated November 2026

Max flow
9.6 GPH
Max head
33 ft
Voltage
115 V spec row; title 115V/230V; brand chart 100V~230V
Switch type
Hall sensor in a separate reservoir, automatic start and stop
Discharge
3/10 in OD barb for 1/4 in to 3/8 in ID vinyl tubing

Each button opens this exact model's listing. We may earn a commission on tracked links; it never changes what we publish. Disclosure

Quick verdict

In short

This suits a wall-mounted ductless unit whose condensate cannot fall to an outside drain. The pump and its tiny reservoir are small enough to tuck into a line set cover or behind the head, and the dual contacts let you either stop the unit or sound an alarm. Its flow is a trickle compared with tank pumps, which is fine for one indoor head but wrong for a furnace.

Who it fits, and who should skip it

A good fit if

  • A ductless wall head where gravity drainage to the outside is not possible.
  • You want the pump hidden in a line set cover or above a ceiling.
  • You need a choice of a shut-off contact or an alarm contact.

Look elsewhere if

  • A furnace, boiler or large air handler that makes a lot of water.
  • Several appliances must share one pump; there is a single inlet.

Specifications

Performance

Max flow9.6 GPH
Max head33 ft
Noise20 dB (listing claim)

Figures: Amazon listing B0G6CR4F7M, Aquastrong CDS036-1.

Motor

Voltage115 V spec row; title 115V/230V; brand chart 100V~230V
Motor protectionThermally protected motor

Figures: Amazon listing B0G6CR4F7M, Aquastrong CDS036-1.

Switch

Switch typeHall sensor in a separate reservoir, automatic start and stop
Safety contactsNC and COM to stop the appliance; NO and COM for an alarm

Figures: Amazon listing B0G6CR4F7M, Aquastrong CDS036-1.

Build

ReservoirVisible tank with filter, 1.2 oz (brand chart)
Inlet3/5 in OD, with a 3/5 in ID silicone tube and a 4/5 in ID adapter
Discharge3/10 in OD barb for 1/4 in to 3/8 in ID vinyl tubing
DimensionsPump 3.4 x 1.8 x 1.8 in; reservoir 4.9 x 1.8 x 2 in (brand chart)
MountingAnti-vibration hook-and-loop strips; reservoir upright, magnet up
Power cord3.3 ft, 3-prong plug

Figures: Amazon listing B0G6CR4F7M, Aquastrong CDS036-1.

Ownership

Cleaning intervalReservoir, float and filter at least every six months
WarrantyNot stated in the listing

Figures: Amazon listing B0G6CR4F7M, Aquastrong CDS036-1.

Versions

The brand chart shows the mini pump alone and with drain tubing. The saved page is the pump-only version.

VersionPart numberWhat differsListing
CDS036, pump only, dark grayCDS036-1Pump and sensor reservoir, inlet tube and adapter, 3.3 ft cordView on Amazon
CDS036 with tubingNot stated in the listingSame pump with 10 ft of vinyl tubing per the brand chartNot linked

Figures: Amazon listing B0G6CR4F7M, Aquastrong CDS036-1.

Installation and setup

The pump comes in two parts joined by a sensor cable: a small reservoir that catches water from the head's drain stub, and the pump body that pushes it out. Fit the reservoir below the drain outlet so water falls into it, and stand it upright with the magnet facing up, as the listing requires; on its side the Hall sensor cannot read the float.

Join the drain stub to the 3/5 in OD inlet with the silicone tube provided, using the 4/5 in ID adapter if the stub is larger. The outlet barb is 3/10 in OD and takes vinyl tubing of 1/4 in to 3/8 in ID. Stick both parts down with the hook-and-loop strips, which also damp vibration in a line set cover, wall cassette or ceiling void.

Choose a contact pair. NC and COM go into the indoor unit's float-switch or shut-off terminals; NO and COM go to an alarm. Plug the 3.3 ft cord into a grounded outlet, which in a line set cover usually means one installed near the head.

Switch and sizing notes

A float in the reservoir carries a magnet that the Hall sensor reads, so the pump starts on rising water and stops when the tank empties, with no exposed switch to stick. If water keeps rising, the safety contact changes state: the normally closed pair opens to stop the head, or the normally open pair closes to trigger an alarm.

Sizing a mini pump is mostly about height and distance. Aquastrong gives 9.6 GPH as the top flow and 33 ft as the most it can lift, with no figures between. One ductless head makes only a modest stream of water, well within that rating, so the real question is how far up and across the tubing goes. Keep the climb near the head and let the long run fall toward the drain.

Ownership and maintenance

The reservoir is tiny, so slime and dust fill it quickly. Clean the tank, float and filter at least every six months, and more often if the head runs in a dusty room or on long cooling seasons. The tank is see-through, which makes a quick look during filter changes easy.

With power off, unclip the reservoir, flush it, wipe the float and clear the filter. Refit it upright, then pour a little water into the head's drain pan and listen for the pump. A short test of the safety contact, by lifting the float, confirms the head stops or the alarm sounds. The listing states no warranty term.

Pros and cons

Pros

  • Small enough for a line set cover or cassette.
  • Both NC and NO safety contacts are provided.
  • Tall 33 ft lift rating for its size.
  • Clear reservoir shows when cleaning is due.

Cons

  • Single inlet, one indoor unit only.
  • No warranty term on the listing.
  • Tiny tank needs frequent cleaning in dirty rooms.

Alternatives worth comparing

Final verdict

The CDS036 is a sound pick for one ductless head that needs a hidden pump and a choice of shut-off or alarm wiring. For furnaces, multiple drains or heavy water, move to a tank pump instead.

Where to buy

Each button opens this exact model's listing. We may earn a commission on tracked links; it never changes what we publish. Disclosure

Questions buyers ask

Where does the Aquastrong CDS036 go on a mini split?

The listing names three spots: inside a line set cover, within a wall cassette, or above a ceiling. The reservoir has to sit below the indoor unit's drain outlet so water can fall into it, and the pump body can sit along the tubing nearby.

Should I use the NC or the NO wires?

Use NC and COM when the indoor unit has terminals for a condensate safety switch, so a full reservoir stops cooling. Use NO and COM for a separate alarm. Leave the unused pair insulated.

Is 9.6 GPH enough?

For a single ductless head it normally is, because one wall unit produces far less water than that in an hour. Long or tall tubing lowers the delivered flow, and the listing gives no curve, so keep the climb short.

Why must the magnet face upward?

The float carries a magnet that the Hall sensor reads through the reservoir wall. Mounted any other way, the sensor may not see the float move, and the pump can fail to start or to stop.