Quick verdict
This is the pump to fit when a furnace, air handler or dehumidifier sits below the nearest drain and the water has to climb a storey or so. The extra motor size over the VCMA-15 buys real flow at height: 48 GPH at 10 ft against 25 GPH. The limit is the small tank and a curve that falls to nothing at 20 ft.
Who it fits, and who should skip it
A good fit if
- Your condensate line has to rise roughly 10 ft to reach a drain or a sink tailpiece.
- You want a float switch that can cut the thermostat circuit if the pump ever stops.
- One pump has to serve a furnace and an air conditioner coil together, using two of its inlets.
Look elsewhere if
- The discharge must climb close to 20 ft, where the maker's table shows the flow reaching zero.
- You need a pump that hides inside a mini-split head or a line-set cover.
Specifications
Motor
| Horsepower | 1/30 HP |
|---|---|
| Voltage | 115 V, 60 Hz (a 230 V version is listed separately) |
| Amps and watts | 1.5 A, 93 W at 115 V |
| Motor type | Thermally protected, fan-cooled; stainless steel shaft |
Figures: Little Giant VCMA-20 Series spec sheet 995125.
Performance
| Max flow | 80 GPH at a 1 ft lift (through the check valve) |
|---|---|
| Max head | 20 ft (6.1 m) shut-off at 115 V |
| Flow at 5 ft | 70 GPH |
| Flow at 10 ft | 48 GPH |
| Shut-off pressure | 8.7 PSI |
Figures: Little Giant VCMA-20 Series spec sheet 995125; Little Giant VCMA-20 Series product page.
Switch
| Switch type | Float-operated automatic pump switch plus a separate overflow (high-water) switch |
|---|---|
| Overflow switch wiring | Two 5 in leads; factory set to NO for equipment shut-down, can be moved to NC for an alarm |
Figures: Little Giant VCMA-20 Series spec sheet 995125; Little Giant VCMA Series owner's manual, Form 998086.
Build
| Discharge | 3/8 in OD barbed adapter with built-in check valve |
|---|---|
| Tank | 1/2 gallon ABS tank with wall-mount tabs |
| Inlets | Three 1-1/8 in openings, two capped |
| Materials | ABS tank, cover and volute; glass-filled polypropylene impeller; acetal check valve |
| Max water temperature | 140 °F (60 °C) |
| Power cord | 6 ft, 3-conductor with grounded plug |
| Weight | 5 lb (2.3 kg) |
| Warranty | 12-month limited |
Figures: Little Giant VCMA-20 Series spec sheet 995125; Little Giant VCMA-20 Series product page; Little Giant VCMA Series owner's manual, Form 998086.
Versions
The VCMA-20 motor and tank come in several versions that differ by voltage, the overflow switch and whether tubing is in the box. Check the item number before you order.
| Version | Part number | What differs | Listing |
|---|---|---|---|
| VCMA-20ULS, 115 V, overflow switch | 554425 | The version on this page; 20 ft shut-off, no tubing | View on Amazon |
| VCMA-20ULST, 115 V, switch and tubing | 554435 | Adds 20 ft of 3/8 in ID vinyl tubing; 6.3 lb | View on Amazon |
| VCMA-20UL, 115 V, no overflow switch | 554421 | Same pump without the high-water switch | View on Amazon |
| VCMA-20ULT, 115 V, tubing, no switch | 554431 | Tubing included, no overflow switch | Not linked |
| VCMA-20ULS, 230 V | 554455 | 0.5 A, 75 W; 17 ft shut-off | Not linked |
| VCMA-20ULST, 230 V | 554461 | Switch and tubing; 17 ft shut-off | Not linked |
Figures: Little Giant VCMA-20 Series spec sheet 995125; Little Giant VCMA-20 Series product page.
Installation and setup
Set the pump on a flat, level surface with its inlets below the coil or furnace drain, and keep the motor vents clear. The tank can also hang from the wall using the slots at each end. Before anything else, pull out the cardboard insert that holds the float during shipping; Little Giant warns that leaving it in makes the tank overflow.
Cut the incoming drain pipes at a 45° angle so they cannot seal against the tank floor, and drop them 1 to 3 inches into the inlet holes without touching the floats. Push tubing of no more than 3/8 in inside diameter onto the check valve and clamp it. Run it straight up, then slope it down toward the drain; if it cannot slope, form an inverted U at the high point. Before the first start, let the air conditioner cycle into a bucket a few times to flush out leftover oil.
Plug the cord into its own constant-power outlet, never one switched with a fan.
Switch and sizing notes
A float inside the tank starts and stops the motor. A second float drives the overflow switch: as shipped it opens the low-voltage thermostat circuit when the water rises too far, so the furnace or air conditioner stops making water. Move the lead from the NO to the NC terminal under the motor cover and the same switch can sound an external alarm or trip a relay instead. Keep it on a Class II low-voltage circuit.
Size from the lift, not the headline flow. The maker's table gives 80 GPH at 1 ft, 70 GPH at 5 ft and 48 GPH at 10 ft. The manual also says not to route the tubing higher than 75% of the pump's total head, which leaves a working margin below the 20 ft shut-off. If the climb is short, the smaller VCMA-15ULS carries the same tank and switch. The condensate pump guide covers matching lift to equipment.
Ownership and maintenance
Little Giant asks for an inspection every six months, more often in heavy use. Unplug the pump, snap off the cover, make sure both floats move freely, then wash the tank with warm water and mild soap. Remove the check valve and backwash the discharge port over a sink, because slime there is a common reason for a pump that runs without emptying.
Condensate from a gas furnace is acidic. The manual asks owners to flush the tank with fresh water so the pH does not fall below 3.4 in one spot, where it can pit the parts. The warranty runs 12 months from purchase.
Pros and cons
Pros
- Nearly double the VCMA-15's flow at a 10 ft lift.
- Overflow switch can stop the equipment or trigger an alarm.
- Check valve and three inlets come built into the tank.
- Item numbers make each version easy to match.
Cons
- Half-gallon tank fills quickly under a large coil.
- Flow falls to zero at the 20 ft shut-off.
- The 230 V version only reaches 17 ft.
Alternatives worth comparing



Compared with and featured in
Final verdict
Buy the VCMA-20ULS when a furnace or air handler needs its condensate lifted about one storey and you want the equipment to shut down rather than flood. For a climb of only a few feet, the smaller VCMA-15ULS does the same job.
Where to buy
Each button opens this exact model's listing. We may earn a commission on tracked links; it never changes what we publish. Disclosure
Questions buyers ask
What is the difference between the VCMA-20ULS and the VCMA-20ULST?
They share the motor, tank and overflow switch. The ULST, item 554435, adds 20 ft of 3/8 in vinyl tubing in the box and weighs a little more. If you already have tubing, the ULS is the same pump.
How do I wire the VCMA-20ULS safety switch?
As shipped, the two black leads use the NO terminal and go in series with the thermostat circuit, so a full tank stops the equipment. To drive an alarm instead, take off the motor cover and move the lead to the NC terminal.
How high can the VCMA-20ULS pump condensate?
The shut-off head is 20 ft on 115 V, but flow at that height is zero. The table shows 48 GPH at 10 ft, and the manual asks you to stay within 75% of total head, so plan the tubing run well below the shut-off.
Can it handle condensate from a high-efficiency furnace?
Yes. Little Giant lists condensing furnaces and boilers among its uses, with water up to 140 °F. Because that condensate is acidic, flush the tank with fresh water during routine cleaning.